Construction
Conductor |
Plain annealed copper, Class 2 Stranded Circular, Compacted or Sectored |
Insulation |
Cross-linked Polyethylene (XLPE) Compound |
Insulation Colour |
2 cores: Brown, Blue or Red, Black
3 cores: Brown, Black, Grey or Red, Yellow, Blue
4 cores: Brown, Black, Grey, Blue or Red, Yellow, Blue, Black
5 cores: Brown, Black, Grey, Blue, Green/Yellow or Red, Yellow, Blue, Black, Green/Yellow or White with Black numbering or Others
|
Assembly |
Cores cabled together with filler and covered with Polyester (PET) Tape |
Outer Sheath |
Low Smoke Zero Halogen (LSZH) Compound |
Outer Sheath Colour |
Black |
Electrical Characteristics
Operating Voltage |
0.6/1kV |
Operating Temperature |
-15°C to 90°C |
Final Short Circuit Temperature |
250C |
Test Voltage |
3.5kV for 5 minutes |
|
Installation Reference
Min. Bending Radius (mm) |
8 x cable overall diameter |
Max. Pulling Tension (N/mm2) |
50 |
Reference Standards
Design Specification |
IEC60502-1 |
Conductor |
IEC60228, BS EN60228 |
Flame Retardancy |
IEC60332-3-22, BS EN60332-3-22 |
Low Smoke Zero Halogen |
IEC61034-2, BS EN61034-2 IEC60754-1,IEC60754-2 BS EN50267-2-1, BS EN50267-2-2 |
|